OBC 2006 › Division B
9.23.10.1.
Version 1 — in force 2 April 2007
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.23.10.1.
- Version
- v1
80. (1) Subject to subsection (2), this Regulation comes into force on the day it is filed.
Read directly from the regulation's own commencement section.
O. Reg. 137/07 · commencement 80(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.23.10.1.
- Version
- v1
80. (1) Subject to subsection (2), this Regulation comes into force on the day it is filed.
Read directly from the regulation's own commencement section.
O. Reg. 137/07 · commencement 80(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 9.23.10.1. — Pro
Base · O. Reg. 350/06 · ext v0 →
O. Reg. 137/07, cl. 66 · ext ← current
In force 2007-04-02
OBC 2012 · continues as 9.23.10.1. — Pro
9.23.10.1. — Stud Size and Spacing
Comparing versions
Changed text stands out · unchanged is dimmed
v0 base
Earlier · 2006-12-31(1) Except as provided in Sentence (2), the size and spacing of studs shall conform to Table 9.23.10.1.
(2) Studs for walls not listed in Table 9.23.10.1. and supporting roof loads shall conform to Table A-30 to A-33, provided,
(a) the studs are clad with not less than 9.5 mm thick plywood, OSB or waferboard sheathing on the exterior face, and not less than 12.5 mm gypsum board on the interior face,
(b) solid bridging is provided at not more than 1 200 mm on centre,
(c) the studs are fastened to the top and bottom plates with no fewer than three 82 mm toe-nails,
(d) the double top plates are fastened together with not less than 76 mm nails spaced not more than 200 mm on centre,
(e) roof framing members spaced not more than 600 mm are fastened to the top plates with no fewer than four 82 mm toe-nails, and
(f) the bottom plate is fastened to the floor joists, blocking or rim joist with not less than 82 mm nails spaced not more than 200 mm on centre.
v1 O. Reg. 137/07
Later · viewing · 2007-04-02(1) Except as provided in Sentence (2), the size and spacing of studs shall conform to Table 9.23.10.1.
(2) Studs for walls not listed in Table 9.23.10.1. and supporting roof loads shall conform to Table A-30 to A-33, provided,
(a) the studs are clad with not less than 9.5 mm thick plywood, OSB or waferboard sheathing on the exterior face, and not less than 12.5 mm gypsum board on the interior face,
(b) solid bridging is provided at not more than 1 200 mm on centre,
(c) the studs are fastened to the top and bottom plates with no fewer than three 82 mm toe-nails,
(d) the double top plates are fastened together with not less than 76 mm nails spaced not more than 200 mm on centre,
(e) roof framing members spaced not more than 600 mm are fastened to the top plates with no fewer than four 82 mm toe-nails, and
(f) the bottom plate is fastened to the floor joists, blocking or rim joist with not less than 82 mm nails spaced not more than 200 mm on centre.