9.22.2.2.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 9.22.2.2. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · continues as 9.22.2.2. — Pro

9.22.2.2. — Firebrick Liners

(1) Fireplace liners shall be not less than,

(a) 50 mm thick for the sides and back, and

(b) 25 mm thick for the floor.

(2) Firebrick liners shall be laid with high temperature cement mortar conforming to CAN/CGSB- 10.3, “Air Setting Refractory Mortar”.

(3) Joints between a firebrick liner and the adjacent back-up masonry shall be offset.