9.22.2. — Fireplace Liners

Content not available for this version.

9.22.2.1. — Brick or Steel Liners

(1) Except where a fireplace is equipped with a steel liner, every fireplace shall have a firebrick liner.

Text · e-Laws consolidated snapshot

9.22.2.2. — Firebrick Liners

(1) Fireplace liners shall be not less than,

(a) 50 mm thick for the sides and back, and

(b) 25 mm thick for the floor.

(2) Firebrick liners shall be laid with high temperature cement mortar conforming to CAN/CGSB- 10.3, “Air Setting Refractory Mortar”.

(3) Joints between a firebrick liner and the adjacent back-up masonry shall be offset.

Text · e-Laws consolidated snapshot

9.22.2.3. — Steel Liners

(1) Steel liners for fireplaces shall conform to CAN/ULC-S639M, “Steel Liner Assemblies for Solid-Fuel Burning Masonry Fireplaces”, and shall be installed in accordance with the installation instructions in that standard.

Text · e-Laws consolidated snapshot