9.21.4. — Masonry and Concrete Chimney Construction

Content not available for this version.

9.21.4.1. — Unit Masonry

(1) Unit masonry shall conform to Section 9.20.

Text · e-Laws consolidated snapshot

9.21.4.2. — Concrete

(1) Concrete shall conform to Section 9.3.

Text · e-Laws consolidated snapshot

9.21.4.3. — Footings

(1) Footings for masonry chimneys and concrete chimneys shall conform to the requirements in Section 9.15.

Text · e-Laws consolidated snapshot

9.21.4.4. — Height of Chimney Flues

(1) A chimney flue shall extend not less than,

(a) 900 mm above the highest point at which the chimney comes in contact with the roof, and

(b) 600 mm above the highest roof surface or structure within 3 m of the chimney.

Text · e-Laws consolidated snapshot

9.21.4.5. — Lateral Stability

(1) Except as provided in Sentence (2), chimneys shall be braced in accordance with Subsection 4.3.2. to provide stability under wind loads.

(2) A chimney need not be laterally braced provided,

(a) no horizontal outside dimension is less than 400 mm, and

(b) the chimney extends not more than 3.6 m above a roof or the masonry wall of which it forms a part.

Text · e-Laws consolidated snapshot

9.21.4.6. — Chimney Caps

(1) The top of a chimney shall have a waterproof cap of reinforced concrete, masonry or metal.

(2) The cap required in Sentence (1) shall slope from the lining and be provided with a drip not less than 25 mm from the chimney wall.

(3) Cast-in-place concrete caps shall be separated from the chimney liner by a bond break and be sealed at that location.

(4) Jointed precast concrete or masonry chimney caps shall have flashing installed beneath the cap extending from the liner to the drip edge.

Text · e-Laws consolidated snapshot

9.21.4.7. — Cleanout

(1) Except for a chimney flue constructed to serve a masonry fireplace, a cleanout opening with a metal frame and tight-fitting metal door shall be installed near the base of the chimney flue.

Text · e-Laws consolidated snapshot

9.21.4.8. — Wall Thickness

(1) The walls of a masonry chimney shall be built of solid units not less than 70 mm thick.

Text · e-Laws consolidated snapshot

9.21.4.9. — Separation of Flue Liners

(1) Flue liners in the same chimney shall be separated by not less than 70 mm of masonry or concrete exclusive of liners where clay liners are used, or 90 mm of firebrick where firebrick liners are used.

(2) Flue liners referred to in Sentence (1) shall be installed to prevent significant lateral movement.

Text · e-Laws consolidated snapshot

9.21.4.10. — Flashing

(1) Junctions with adjacent materials shall be adequately flashed to shed water.

Text · e-Laws consolidated snapshot