OBC 2006 › Division B
9.17.4.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.17.4.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.17.4.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 9.17.4. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 9.17.4. — Pro
9.17.4. — Wood Columns
Content not available for this version.
9.17.4.1. — Column Sizes
(1) The width or diameter of a wood column shall be not less than the width of the supported member.
(2) Except as provided in Article 9.35.4.2., columns shall be not less than 184 mm for round columns and 140 mm by 140 mm for rectangular columns, unless calculations are provided to show that lesser sizes are adequate.
Text · e-Laws consolidated snapshot
9.17.4.2. — Materials
(1) Wood columns shall be either solid, glue-laminated or built-up.
(2) Built-up columns shall consist of not less than 38 mm thick full-length members,
(a) bolted together with not less than 9.52 mm diam bolts spaced not more than 450 mm o.c., or
(b) nailed together with not less than 76 mm nails spaced not more than 300 mm o.c.
(3) Glued-laminated columns shall conform to Section 4.3.
Text · e-Laws consolidated snapshot
9.17.4.3. — Columns in Contact with Concrete
(1) Wood columns shall be separated from concrete in contact with the ground by 0.05 mm polyethylene film or Type S roll roofing.
Text · e-Laws consolidated snapshot
9.17.4.4. — Wood Column Termite Protection
(1) Where termites are known to exist, exterior wood columns such as porch supports shall be,
(a) pressure-treated with a chemical that is toxic to such termites, in accordance with Article 9.3.2.9.v1v2, or
(b) supported on non-cellulosic material extending not less than 150 mm above grade and located not less than 50 mm from the exterior wall of an adjacent building.