OBC 2006 Division B

9.10.19.3.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · renumbered from 9.10.18.3. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · renumbered to 9.10.19.4. — Pro

9.10.19.3. — Power Supply

(1) Except as permitted in Sentence (2), smoke alarms shall be installed by permanent connections to an electrical circuit and shall have no disconnect switch between the overcurrent circuit device and the smoke alarm.

(2) Where the building is not supplied with electrical power, smoke alarms are permitted to be battery operated.

Text · e-Laws consolidated snapshot