OBC 2006 › Division B
9.10.19.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.10.19.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.10.19.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · renumbered from 9.10.18. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 9.10.19. — Pro
9.10.19. — Smoke Alarms
Content not available for this version.
9.10.19.1. — Required Smoke Alarms
(1) Smoke alarms conforming to CAN/ULC-S531, “Smoke Alarms”, shall be installed in each dwelling unit and in each sleeping room not within a dwelling unit.
Text · e-Laws consolidated snapshot
9.10.19.2. — Location of Smoke Alarms
(1) Within dwelling units, sufficient smoke alarms shall be installed so that,
(a) there is at least one smoke alarm on each floor level, including basements, that is 900 mm or more above or below an adjacent floor level,
(b) each bedroom is protected by a smoke alarm either inside the bedroom or, if outside, within 5 m, measured following corridors and doorways, of the bedroom door, and
(c) the distance, measured following corridors and doorways, from any point on a floor level to a smoke alarm on the same level does not exceed 15 m.
(2) Smoke alarms required in Article 9.10.19.1. and Sentence (1) shall be installed on or near the ceiling.
(3) Smoke alarms required in Sentences (1) and (2) shall be audible within the bedrooms when the intervening doors are closed.
(4) Smoke alarms required in Sentences (1) and (2) shall be installed in conformance with the manufacturers instructions.
Text · e-Laws consolidated snapshot
9.10.19.3. — Power Supply
(1) Except as permitted in Sentence (2), smoke alarms shall be installed by permanent connections to an electrical circuit and shall have no disconnect switch between the overcurrent circuit device and the smoke alarm.
(2) Where the building is not supplied with electrical power, smoke alarms are permitted to be battery operated.
Text · e-Laws consolidated snapshot
9.10.19.4. — Interconnection of Smoke Alarms
(1) Where more than one smoke alarm is required in a dwelling unit, the smoke alarms shall be wired so that the activation of one alarm will cause all alarms within the dwelling unit to sound.
Text · e-Laws consolidated snapshot
9.10.19.5. — Instructions for Maintenance and Care
(1) Where instructions are necessary to describe the maintenance and care required for smoke alarms to ensure continuing satisfactory performance, they shall be posted in a location where they will be readily available to the occupants for reference.
Text · e-Laws consolidated snapshot
9.10.19.6. — Silencing of Alarm Noise
(1) A manually operated device is permitted to be incorporated within the circuitry of a smoke alarm installed in a dwelling unit so that it will silence the signal emitted by the smoke alarm for a period of not more than 10 min, after which the smoke alarm will reset and again sound the alarm if the level of smoke in the vicinity is sufficient to reactuate the smoke alarm.
Text · e-Laws consolidated snapshot