9.10.10.7. — Emergency Power Installations

(1) A generator to supply emergency power for lighting and fire safety systems shall be located in a room that,

(a) is separated from the remainder of the building by a fire separation with a fire-resistance rating not less than,

(i) 1 h, if the floor assembly is not required to have a fire-resistance rating of more than 1 h, and

(ii) 2 h, if the floor assembly is required to have a fire-resistance rating of more than 1 h, and

(b) contains only the generating set and equipment that is related to the emergency power supply system.