9.10.10. — Service Rooms

Content not available for this version.

9.10.10.1. — Application

(1) This Subsection applies to service rooms in all buildings except rooms located within a dwelling unit.

Text · e-Laws consolidated snapshot

9.10.10.2. — Service Room Floors

(1) The fire-resistance rating requirements in this Subsection do not apply to the floor assembly immediately below a service room.

Text · e-Laws consolidated snapshot

9.10.10.3. — Separation of Service Rooms

(1) Except as required in Sentence (2) and Articles 9.10.10.5. and 9.10.10.6., service rooms shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 1 h when the floor area containing the service room is not sprinklered.

(2) Where a room contains a limited quantity of service equipment and the service equipment does not constitute a fire hazard, the requirements in Sentence (1) shall not apply.

Text · e-Laws consolidated snapshot

9.10.10.4. — Appliances and Equipment to be Located in a Service Room

(1) Except as provided in Sentence (2) and Article 9.10.10.5., fuel-fired appliances other than fireplaces shall be located in a service room separated from the remainder of the building by a fire separation having not less than a 1 h fire-resistance rating.

(2) Except as required in the appliance installation standards referenced in Sentences 6.2.1.4.(1) and 9.33.1.2.(1), fuel-fired space-heating appliances, space-cooling appliances and service water heaters need not be separated from the remainder of the building as required in Sentence (1) where the equipment serves,

(a) not more than one room or suite, or

(b) a building with a building area of not more than 400 m² and a building height of not more than 2 storeys.

Text · e-Laws consolidated snapshot

9.10.10.5. — Incinerators

(1) Service rooms containing incinerators shall be separated from the remainder of the building by a fire separation having a fire-resistance rating of not less than 2 h.

(2) The design, construction, installation and alteration of each indoor incinerator shall conform to NFPA 82, “Incinerators, Waste and Linen Handling Systems and Equipment”.

(3) Every incinerator shall be connected to a chimney flue conforming to the requirements in Section 9.21. and serving no other appliance.

(4) An incinerator shall not be located in a room with other fuel-fired appliances.

Text · e-Laws consolidated snapshot

9.10.10.6. — Storage Rooms

(1) Rooms for the temporary storage of combustible refuse in all occupancies or for public storage in residential occupancies shall be separated from the remainder of the building by a fire separation having not less than a 1 h fire-resistance rating, except that a 45 min fire separation is permitted where the fire-resistance rating of the floor assembly is not required to exceed 45 min, or where such rooms are sprinklered.

Text · e-Laws consolidated snapshot

9.10.10.7. — Emergency Power Installations

(1) A generator to supply emergency power for lighting and fire safety systems shall be located in a room that,

(a) is separated from the remainder of the building by a fire separation with a fire-resistance rating not less than,

(i) 1 h, if the floor assembly is not required to have a fire-resistance rating of more than 1 h, and

(ii) 2 h, if the floor assembly is required to have a fire-resistance rating of more than 1 h, and

(b) contains only the generating set and equipment that is related to the emergency power supply system.

Text · e-Laws consolidated snapshot