7.5.4.5. — Fixtures Draining into Vent Pipes

Comparing versions

Changed text stands out · unchanged is dimmed

v0 base

Earlier · viewing · 2006-12-31

(1) The trap arm of a fixture that has a hydraulic load of not more than 1 ½ fixture units may be connected to the vertical section of a circuit vent, additional circuit vent, offset relief vent, relief vent or yoke vent, provided that,

(a) not more than 2 fixtures are connected to the vent pipe,

(b) where 2 fixtures are connected to the vent pipe, the connection is by means of a double sanitary T fitting, and

(c) the section of the vent pipe that acts as a wet vent conforms to the requirements regarding wet vents.

v1 O. Reg. 503/09

Later · 2010-01-01

(1) The trap arm of a fixture that has a hydraulic load of not more than 1 ½ fixture units may be connected to the vertical section of a circuit vent, additional circuit vent, offset relief vent or yoke vent, provided that,

(a) not more than 2 fixtures are connected to the vent pipe,

(b) where 2 fixtures are connected to the vent pipe, the connection is by means of a double fitting, in accordance with Table 7.2.4.5., and

(c) the section of the vent pipe that acts as a wet vent conforms to the requirements regarding wet vents.