CodeChronicle

OBC 2006 Division B

5.10.1.1.

Version 1 — in force 1 January 2010

In force · amended
Verified · covered Verified against the 2010-01-01–2010-03-31 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · split from 5.3.1.2. — Pro

OBC 1997 · split from 5.4.1.2. — Pro

OBC 1997 · split from 5.6.1.2. — Pro

OBC 1997 · split from 5.8.2.2. — Pro

Base · O. Reg. 350/06 · ext v0 →

O. Reg. 503/09, cl. 73(9) · ext ← current

In force 2010-01-01

OBC 2012 · continues as 5.10.1.1. — Pro

5.10.1.1. — Compliance with Applicable Standards

Comparing versions

Changed text stands out · unchanged is dimmed

v0 base

Earlier · 2006-12-31

(1) Except as provided in Sentences (2) and (3) and elsewhere in this Part, materials and components, and their installation, shall conform to the requirements of the applicable standards in Table 5.10.1.1. where those materials or components are,

(a) incorporated into environmental separators or assemblies exposed to the exterior, and

(b) installed to fulfill the requirements of this Part.

(2) The requirements for flame-spread ratings contained in thermal insulation standards shall be applied only as required in Part 3.

(3) Where a wired glass assembly is installed in a required fire separation, the assembly need not conform to CAN/CSA-A440, “Windows”, or CAN/CSA-A440.1, “User Selection Guide to CSA Standard CAN/CSA-A440-00, Windows”.

(4) Skylights not covered in the scope of CAN/CGSB-63.14-M, “Plastic Skylights”, shall nonetheless conform to the performance requirements of that standard.

O. Reg. 350/06, Division B, Part 5.

v1 O. Reg. 503/09

Later · viewing · 2010-01-01

(1) Except as provided in Sentences (2) and (3) and elsewhere in this Part, materials and components, and their installation, shall conform to the requirements of the applicable standards in Table 5.10.1.1. where those materials or components are,

(a) incorporated into environmental separators or assemblies exposed to the exterior, and

(b) installed to fulfill the requirements of this Part.

(2) The requirements for flame-spread ratings contained in thermal insulation standards shall be applied only as required in Part 3.

(3) Where a wired glass assembly is installed in a required fire separation, the assembly need not conform to CAN/CSA-A440, “Windows”, or CAN/CSA-A440.1, “User Selection Guide to CSA Standard CAN/CSA-A440-00, Windows”.

(4) Skylights not covered in the scope of CAN/CGSB-63.14-M, “Plastic Skylights”, shall nonetheless conform to the performance requirements of that standard.

O. Reg. 350/06, Division B, Part 5; O. Reg. 503/09, ss. 69-73.