OBC 2006 › Division B
3.9.3.4.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.9.3.4.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.9.3.4.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 3.9.3.4. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 3.9.3.4. — Pro
3.9.3.4. — Provisions for Fire Fighting
(1) The requirements in Articles 3.2.2.10. and 3.2.5.1. to 3.2.5.7. need not be provided where there are not more than 12 portable classrooms on a site and where,
(a) the distance between portable classrooms is 6 m or more,
(b) the distance between portable classrooms is less than 6 m and the requirements of Subsection 3.2.3. are applied between the classrooms,
(c) the portable classrooms are in groups where,
(i) the distance between the classrooms is less than 6 m,
(ii) the number of classrooms in a group is not more than 6,
(iii) within a group of classrooms, the facing walls have a fire-resistance rating of 45 min, rated from inside the classroom, and
(iv) the distance between groups of classrooms is 12 m or more,
(d) the portable classrooms are in groups where,
(i) the distance between the classrooms is less than 6 m,
(ii) the number of classrooms in a group is not more than 6, and
(iii) the distance between groups of classrooms is 12 m or more, or
(e) the portable classrooms are in groups where,
(i) the means of egress for each classroom within a group is by a common corridor or passageway,
(ii) the number of classrooms in a group is not more than 6, and
(iii) the distance between groups of classrooms is 12 m or more.