3.9.3.4. — Provisions for Fire Fighting

(1) The requirements in Articles 3.2.2.10. and 3.2.5.1. to 3.2.5.7. need not be provided where there are not more than 12 portable classrooms on a site and where,

(a) the distance between portable classrooms is 6 m or more,

(b) the distance between portable classrooms is less than 6 m and the requirements of Subsection 3.2.3. are applied between the classrooms,

(c) the portable classrooms are in groups where,

(i) the distance between the classrooms is less than 6 m,

(ii) the number of classrooms in a group is not more than 6,

(iii) within a group of classrooms, the facing walls have a fire-resistance rating of 45 min, rated from inside the classroom, and

(iv) the distance between groups of classrooms is 12 m or more,

(d) the portable classrooms are in groups where,

(i) the distance between the classrooms is less than 6 m,

(ii) the number of classrooms in a group is not more than 6, and

(iii) the distance between groups of classrooms is 12 m or more, or

(e) the portable classrooms are in groups where,

(i) the means of egress for each classroom within a group is by a common corridor or passageway,

(ii) the number of classrooms in a group is not more than 6, and

(iii) the distance between groups of classrooms is 12 m or more.