OBC 2006 › Division B
3.9.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.9.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.9.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 3.9. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 3.9. — Pro
3.9. — Portable Classrooms
Content not available for this version.
3.9.1. — Scope
Content not available for this version.
3.9.1.1. — Application
(1) Except as provided in this Section, the requirements in this Division apply to portable classrooms.
Text · e-Laws consolidated snapshot
3.9.1.2. — Heating Systems
(1) Heating systems and equipment in a portable classroom shall be designed and installed in accordance with Section 6.2.
Text · e-Laws consolidated snapshot
3.9.2. — Interior Finish
Content not available for this version.
3.9.2.1. — Flame-Spread Rating
(1) Interior finish material used on a wall or ceiling of a portable classroom shall have a flame-spread rating of 150 or less.
Text · e-Laws consolidated snapshot
3.9.3. — Application
Content not available for this version.
3.9.3.1. — Building Areas
(1) A single portable classroom shall be not more than 100 m2 in building area, and not more than 1 storey in building height.
(2) For the purposes of Subsection 3.2.2., where the horizontal distance between portable classrooms is less than 6 m, a group of portable classrooms may be considered as a single building with a building area equal to the aggregate area of the portable classrooms.
Text · e-Laws consolidated snapshot
3.9.3.2. — Spatial Separations
(1) The requirements in Subsection 3.2.3. need not be provided between individual portable classrooms where the distance between the classrooms is 6 m or more.
(2) The requirements in Subsection 3.2.3. need not be provided between individual portable classrooms within a group where,
(a) the portable classrooms are in groups where ,
(i) the distance between the classrooms is less than 6 m,
(ii) the number of classrooms in a group is not more than 6, and
(iii) the distance between groups of classrooms is 12 m or more, or
(b) the portable classrooms are in groups where,
(i) the means of egress for each classroom within a group is by a common corridor or passageway,
(ii) the number of portable classrooms in a group is not more than 6, and
(iii) the distance between groups of portable classrooms is 12 m or more.
Text · e-Laws consolidated snapshot
3.9.3.3. — Fire Alarm Systems
(1) Except as provided in Sentences (2) and (3), the fire alarm system in the main school building shall be extended to the portable classrooms with a separate zone indicator on the annunciator.
(2) The requirements in Sentence (1) need not be provided where there are not more than 12 portables on a site and where,
(a) reserved,
(b) the distance between portable classrooms is less than 6 m and the requirements of Subsection 3.2.3. are applied between the classrooms, or
(c) the portable classrooms are in groups where,
(i) the distance between the classrooms is less than 6 m,
(ii) the number of classrooms in a group does not exceed 6,
(iii) within a group of classrooms, the facing walls have a fire-resistance rating of 45 min, rated from inside the classroom, and
(iv) the distance between groups of classrooms is 12 m or more.
(3) The requirements in Sentence (1) need not be provided where the distance between portable classrooms is 6 m or more.
Editor's note
As filed in O. Reg. 350/06, Clause (2)(a) of this article reads 'reserved,' (lower case, with a trailing comma). The consolidated e-Laws text capitalizes the word and drops the comma ('Reserved'); this change was not enacted by any amending regulation, and the as-filed text is retained here.
3.9.3.4. — Provisions for Fire Fighting
(1) The requirements in Articles 3.2.2.10. and 3.2.5.1. to 3.2.5.7. need not be provided where there are not more than 12 portable classrooms on a site and where,
(a) the distance between portable classrooms is 6 m or more,
(b) the distance between portable classrooms is less than 6 m and the requirements of Subsection 3.2.3. are applied between the classrooms,
(c) the portable classrooms are in groups where,
(i) the distance between the classrooms is less than 6 m,
(ii) the number of classrooms in a group is not more than 6,
(iii) within a group of classrooms, the facing walls have a fire-resistance rating of 45 min, rated from inside the classroom, and
(iv) the distance between groups of classrooms is 12 m or more,
(d) the portable classrooms are in groups where,
(i) the distance between the classrooms is less than 6 m,
(ii) the number of classrooms in a group is not more than 6, and
(iii) the distance between groups of classrooms is 12 m or more, or
(e) the portable classrooms are in groups where,
(i) the means of egress for each classroom within a group is by a common corridor or passageway,
(ii) the number of classrooms in a group is not more than 6, and
(iii) the distance between groups of classrooms is 12 m or more.
Text · e-Laws consolidated snapshot
3.9.3.5. — Portable Fire Extinguishers
(1) A fire extinguisher, in accordance with Article 3.2.5.17.v1, shall be installed in each portable classroom.
Text · e-Laws consolidated snapshot
3.9.3.6. — Means of Egress
(1) Except as required in Sentence 3.9.3.7.(1), a portable classroom shall be provided with means of egress conforming to Sections 3.3. and 3.4.
Text · e-Laws consolidated snapshot
3.9.3.7. — Fuel-Fired Appliances
(1) Where there is only one egress door from a portable classroom, a fuel-fired appliance shall be separated from the remainder of the classroom by a fire separation with a fire-resistance rating of not less than 45 min.
(2) Except as provided in Sentences (3) and (4), if a portable classroom contains a fuel-fired appliance, the appliance shall be separated from the remainder of the classroom by a fire separation having a fire-resistance rating not less than,
(a) 1.5 h where the horizontal distance between portable classrooms is 1 500 mm or less, and
(b) 45 min where the horizontal distance between portable classrooms is more than 1 500 mm.
(3) If the horizontal distance between portable classrooms is 6 m or more, a fuel-fired appliance need not be separated from the remainder of the classroom by a fire separation provided,
(a) there is not more than 1 appliance per portable classroom, and
(b) the appliance is located not less than 4.5 m from an egress doorway or an exit from the portable classroom.
(4) Fuel-fired appliances with sealed combustion located in a portable classroom are not required to be separated from the remainder of the classroom,
(a) if there are not more than four portable classrooms in a group, and
(b) if the appliance is located not less than 4.5 m from an egress doorway or an exit from the portable classroom.
Text · e-Laws consolidated snapshot
3.9.3.8. — Washroom Facilities
(1) Washroom facilities need not be provided in a portable classroom where the facilities in the main school building comply with the requirements of Subsection 3.7.4. for the total occupant load of the main school building and the portable classrooms.
Text · e-Laws consolidated snapshot
3.9.3.9. — Barrier-Free Access
(1) The requirements of Section 3.8. for barrier-free access need not be provided for a portable classroom provided that the main school building complies with the requirements of Section 3.8.