(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.4.6.4.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
Provenance
OBC 1997 · continues from 3.4.6.4. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
O. Reg. 503/09, cl. 44 · ext v1 →
In force 2010-01-01
Next: O. Reg. 503/09, cl. 44 · ext (not in force until 2010-01-01) v1 →
OBC 2012 · renumbered to 3.4.6.5. — Pro
3.4.6.4. — Handrails
Comparing versions
Changed text stands out · unchanged is dimmed
v0 base
Earlier · viewing · 2006-12-31(1) A ramp or stairway shall have a handrail on at least one side, and if 1 100 mm or more in width, shall have handrails on both sides.
(2) If the required width of a ramp or flight of stairs is more than 2 200 mm, one or more intermediate handrails continuous between landings shall be provided, and located so that there will be not more than 1 650 mm between handrails.
(3) Handrails shall be continuously graspable along their entire length and shall have,
(a) a circular cross-section with an outside diameter not less than 30 mm and not more than 43 mm, or
(b) any non-circular shape with a graspable portion that has a perimeter not less than 100 mm and not more than 125 mm and whose largest cross-sectional dimension is not more than 45 mm.
(4) Handrails on stairs and ramps shall be not less than 865 mm and not more than 965 mm high, measured vertically from a line drawn through the outside edges of the stair nosing or from the surface of the ramp, except that handrails not meeting these requirements are permitted provided they are installed in addition to the required handrail.
(5) Except as required by Sentence (11) and except where interrupted by doorways or newels at changes in direction, at least one handrail shall be continuous throughout the length of a stairway or ramp, including landings.
(6) Handrails shall be terminated in a manner that will not obstruct pedestrian travel or create a hazard.
(7) At least one handrail shall,
(a) in the case of a stair,
(i) extend horizontally at the required height, not less than 300 mm beyond the top riser, and
(ii) continue to slope for a depth of one tread beyond the bottom riser followed by a 300 mm horizontal extension, and
(b) in the case of a ramp, extend horizontally at the required height, not less than 300 mm beyond the top and bottom edges of the incline.
(8) The clearance between a handrail and any surface behind it shall be not less than 50 mm.
(9) Handrails and their supports shall be designed and constructed to withstand the loading values obtained from the nonconcurrent application of,
(a) a concentrated load not less than 0.9 kN applied at any point and in any direction for all handrails, and
(b) a uniform load not less than 0.7 kN/m applied in any direction to handrails not located within dwelling units.
(10) A ramp shall have handrails on both sides.
(11) In a nursing home, a home for the aged and a Group B, Division 3 occupancy, a continuous handrail shall be provided on both sides of a stairway throughout the length of the stairway, including landings, except where a handrail is interrupted by doorways or newels at changes in direction.
v1 O. Reg. 503/09
Later · 2010-01-01(1) A stairway shall have a handrail on at least one side, and if 1 100 mm or more in width, shall have handrails on both sides.
(2) If the required width of a ramp or flight of stairs is more than 2 200 mm, one or more intermediate handrails continuous between landings shall be provided, and located so that there will be not more than 1 650 mm between handrails.
(3) Handrails shall be continuously graspable along their entire length and shall have,
(a) a circular cross-section with an outside diameter not less than 30 mm and not more than 43 mm, or
(b) any non-circular shape with a graspable portion that has a perimeter not less than 100 mm and not more than 125 mm and whose largest cross-sectional dimension is not more than 45 mm.
(4) Handrails on stairs and ramps shall be not less than 865 mm and not more than 965 mm high, measured vertically from a line drawn through the outside edges of the stair nosing or from the surface of the ramp, except that handrails not meeting these requirements are permitted provided they are installed in addition to the required handrail.
(5) Except as required by Sentence (11) and except where interrupted by doorways or newels at changes in direction, at least one handrail shall be continuous throughout the length of a stairway or ramp, including landings.
(6) Handrails shall be terminated in a manner that will not obstruct pedestrian travel or create a hazard.
(7) At least one handrail shall,
(a) in the case of a stair,
(i) extend horizontally at the required height, not less than 300 mm beyond the top riser, and
(ii) continue to slope for a depth of one tread beyond the bottom riser followed by a 300 mm horizontal extension, and
(b) in the case of a ramp, extend horizontally at the required height, not less than 300 mm beyond the top and bottom edges of the incline.
(8) The clearance between a handrail and any surface behind it shall be not less than 50 mm.
(9) Handrails and their supports shall be designed and constructed to withstand the loading values obtained from the nonconcurrent application of,
(a) a concentrated load not less than 0.9 kN applied at any point and in any direction for all handrails, and
(b) a uniform load not less than 0.7 kN/m applied in any direction to handrails not located within dwelling units.
(10) A ramp shall have handrails on both sides.
(11) In a nursing home, a home for the aged and a Group B, Division 3 occupancy, a continuous handrail shall be provided on both sides of a stairway throughout the length of the stairway, including landings, except where a handrail is interrupted by doorways or newels at changes in direction.