3.2.8.8. — Fire Alarm and Detection System

(1) A building containing an interconnected floor space shall be provided with,

(a) a fire alarm system and electrically supervised annunciator conforming to Subsection 3.2.4.,

(b) a system of smoke detectors located,

(i) on the ceiling of each storey in the vicinity of the openings through floor assemblies described in Article 3.2.8.3., except within dwelling units, heat detectors may be installed instead of smoke detectors, and

(ii) as required for the activation of the smoke control system described in Sentences 3.2.8.9.(3), (4), (6) and (7), and

(c) facilities for transmitting a signal to the fire department in conformance with Article 3.2.4.7.