CodeChronicle

OBC 2006 Division B

3.2.6.7.

Version 1 — in force 1 April 2010

In force · amended
Verified · covered Verified against the 2010-04-01–2010-06-30 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 3.2.6.7. — Pro

Base · O. Reg. 350/06 · ext v0 →

O. Reg. 205/08, cl. 7 · ext ← current

In force 2010-04-01

OBC 2012 · continues as 3.2.6.7. — Pro

3.2.6.7. — Central Alarm and Control Facility

Comparing versions

Changed text stands out · unchanged is dimmed

v0 base

Earlier · 2006-12-31

(1) If a building described in Sentence 3.2.6.1.(1) is connected to any other building, measures shall be taken to limit movement of contaminated air from one building into another during a fire.

v1 O. Reg. 205/08

Later · viewing · 2010-04-01

(1) A central alarm and control facility shall be provided on the storey containing the entrance for fire fighter access referred to in Articles 3.2.5.4. and 3.2.5.5. in a location that,

(a) is readily accessible to fire fighters entering the building, and

(b) takes into account the effect of background noise likely to occur under fire emergency conditions, so that the facility can properly perform its required function under such conditions.

(2) The central alarm and control facility required in Sentence (1) shall include,

(a) means to control the voice communication system required by Article 3.2.6.8., so that messages can be sent to,

(i) all loudspeakers simultaneously,

(ii) individual floor areas, and

(iii) exit stairwells,

(b) means to indicate audibly and visually alert signals and alarm signals and a switch to,

(i) silence the audible portion of these signals, and

(ii) indicate visually that the audible portion has been silenced,

(c) means to indicate visually that elevators are on emergency recall,

(d) an annunciator conforming to Article 3.2.4.8.,

(e) means to transmit alert signals and alarm signals to the fire department in conformance with Article 3.2.4.7.,

(f) means to release hold-open devices on doors to vestibules,

(g) means to manually actuate alarm signals in the building selectively to any zone or zones,

(h) means to silence the alarm signals referred to in Clause (g) in conformance with Sentences 3.2.4.22.(2) and (3),

(i) means, as appropriate to the measure for fire safety provided in the building, to,

(i) actuate auxiliary equipment, or

(ii) communicate with a continually staffed auxiliary equipment control centre,

(j) means to communicate with every elevator car,

(k) means to indicate visually, individual sprinkler system waterflow signals,

(l) means to indicate audibly and visually, sprinkler system supervisory signals and trouble signals,

(m) a switch to silence the audible portion of a supervisory signal or a trouble signal, and

(n) visual indication that the audible portion of a supervisory signal or a trouble signal has been silenced.