OBC 2006 › Division B
3.2.6.4.
Version 1 — in force 1 April 2010
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.2.6.4.
- Version
- v1
15. This Regulation comes into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 205/08 · commencement 15
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.2.6.4.
- Version
- v1
15. This Regulation comes into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 205/08 · commencement 15
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 3.2.6.4. — Pro
Base · O. Reg. 350/06 · ext v0 →
O. Reg. 205/08, cl. 7 · ext ← current
In force 2010-04-01
OBC 2012 · continues as 3.2.6.4. — Pro
3.2.6.4. — Emergency Operation of Elevators
(1) Manual emergency recall shall be provided for all elevators serving storeys above the first storey.
(2) Key-operated switches for emergency recall described by Sentence (1) shall be provided in a conspicuous location at,
(a) each elevator lobby on the recall level, and
(b) the central alarm and control facility required in Article 3.2.6.7.v1
(3) In-car emergency service switches shall be provided in all elevator cars.
(4) Keys to operate the switches required by Sentences (2) and (3) shall be,
(a) provided in a suitably identified box conspicuously located on the outside of an elevator hoistway near the central alarm and control facility required by Article 3.2.6.7.v1, and
(b) kept at the central alarm and control facility.
(5) In a building that is not sprinklered, automatic emergency recall operation shall be provided for all elevators serving storeys above the first storey.
(6) The automatic emergency recall feature in Sentence (5) shall be actuated by,
(a) smoke detectors installed in each elevator lobby on each storey, or
(b) the building fire alarm system.
(7) Smoke detectors in Sentence (6) shall be designed as part of the building fire alarm system.
Text · e-Laws consolidated snapshot
Provenance
OBC 1997 · continues from 3.2.6.4. — Pro
Base · O. Reg. 350/06 · ext v0 → compare
O. Reg. 205/08, cl. 7 · ext ← current
In force 2010-04-01
OBC 2012 · continues as 3.2.6.4. — Pro