3.2.3.19. — Walkway between Buildings

(1) Except as required by Sentence 3.2.3.20.(2), if buildings are connected by a walkway, each building shall be separated from the walkway by a fire separation with a fire-resistance rating not less than 45 min.

(2) Except as permitted by Sentence (3), a walkway connected to a building required to be of noncombustible construction shall also be of noncombustible construction.

(3) A walkway connected to a building required to be of noncombustible construction is permitted to be of heavy timber construction provided,

(a) not less than 50% of the area of any enclosing perimeter walls is open to the outdoors, and

(b) the walkway is at ground level.

(4) A walkway of noncombustible construction used only as a pedestrian thoroughfare need not conform to the requirements of Articles 3.2.3.14. and 3.2.3.15.

(5) A walkway between buildings shall be not more than 9 m wide.