OBC 2006 › Division B
3.2.2.44.
Version 1 — in force 1 April 2010
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.2.2.44.
- Version
- v1
(5) Sections 23, 26 and 31, subsection 32 (2), sections 36, 40, 45, 46 and 48 and subsection 214 (2) come into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(5)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.2.2.44.
- Version
- v1
(5) Sections 23, 26 and 31, subsection 32 (2), sections 36, 40, 45, 46 and 48 and subsection 214 (2) come into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(5)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
New in this edition — no OBC 1997 predecessor
Base · O. Reg. 350/06 · ext v0 →
O. Reg. 503/09, cl. 26 · ext ← current
In force 2010-04-01
OBC 2012 · continues as 3.2.2.44. — Pro
3.2.2.44. — Group C, up to 4 Storeys, Noncombustible Construction
(1) A building classified as Group C is permitted to conform to Sentence (2) provided,
(a) it is not more than,
(i) 3 storeys in building height, or
(ii) 4 storeys in building height provided there is not more than one dwelling unit above another dwelling unit, and vertical fire separations of adjacent dwelling units conform to Sentence (4), and
(b) it has a building area not more than the value in Table 3.2.2.44.
(2) The building referred to in Sentence (1) shall be of noncombustible construction, and,
(a) except as permitted by Sentence (3), floor assemblies shall be fire separations with a fire-resistance rating not less than 1 h,
(b) mezzanines shall have a fire-resistance rating not less than 1 h,
(c) roof assemblies shall have a fire-resistance rating not less than 1 h, and
(d) loadbearing walls, columns and arches shall have a fire-resistance rating not less than that required for the supported assembly.
(3) In a building that contains dwelling units that have more than 1 storey, subject to the requirements of Sentence 3.3.4.2.(3), the floor assemblies, including floors over basements, which are entirely contained within these dwelling units, shall have a fire-resistance rating not less than 1 h but need not be constructed as fire separations.
(4) The dwelling units described in Subclause (1)(a)(ii) shall be separated by continuous vertical fire separations that extend through all storeys and service spaces of the separated portions.
Column 1 | Column 2 | Column 3 | Column 4 |
No. of Storeys | Maximum Area, m2 | ||
Facing 1 Street | Facing 2 Streets | Facing 3 Streets | |
1 | not limited | not limited | not limited |
2 | 6 000 | not limited | not limited |
3 | 4 000 | 5 000 | 6 000 |
4 | 3 000 | 3 750 | 4 500 |