OBC 2006 › Division B
3.2.1.4.
Version 1 — in force 1 April 2010
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.2.1.4.
- Version
- v1
15. This Regulation comes into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 205/08 · commencement 15
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.2.1.4.
- Version
- v1
15. This Regulation comes into force on April 1, 2010.
Read directly from the regulation's own commencement section.
O. Reg. 205/08 · commencement 15
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 3.2.1.4. — Pro
Base · O. Reg. 350/06 · ext v0 →
O. Reg. 205/08, cl. 3 · ext ← current
In force 2010-04-01
OBC 2012 · continues as 3.2.1.4. — Pro
3.2.1.4. — Floor Assembly over Basement
(1) Except as permitted by Sentences 3.2.2.42.(3)v2, 3.2.2.43.(3)v1, 3.2.2.44.(3)v1, 3.2.2.45.(3), 3.2.2.46.(3), 3.2.2.47.(3) or 3.2.2.48.(3), a floor assembly immediately above a basement shall be constructed as a fire separation having a fire-resistance rating conforming to the requirements of Articles 3.2.2.20. to 3.2.2.83. for a floor assembly, but not less than 45 min.
(2) All loadbearing walls, columns and arches supporting a floor assembly immediately above a basement shall have a fire-resistance rating not less than that required by Sentence (1) for the floor assembly.
Editor's note
As filed in O. Reg. 350/06, the list in Sentence (1) of this article is introduced by 'Except as permitted by Sentences ...' (plural). The consolidated e-Laws text renders this in the singular ('Except as permitted by Sentence ...'); this wording difference was not enacted by any amending regulation, and the as-filed text is retained here. (The cross-reference '3.2.2.44.(3)' added to the list by O. Reg. 205/08, s. 3 is applied in this version.)