240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 3.10.3.4.
- Version
- v1
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 3.10.3.4. — Pro
Base · O. Reg. 350/06 · ext v0 →
O. Reg. 503/09, cl. 55 · ext ← current
In force 2010-01-01
OBC 2012 · continues as 3.10.3.4. — Pro
3.10.3.4. — Provisions for Fire Fighting
Comparing versions
Changed text stands out · unchanged is dimmed
v0 base
Earlier · 2006-12-31(1) Except as provided in Sentences (2) to (4), the requirements in Subsection 3.2.5. shall apply.
(2) Access routes for fire department vehicles shall be provided and shall be not less than 9 m wide.
(3) Hydrants shall be located in the access routes required in Sentence (2) so that,
(a) for a building provided with a fire department connection for a standpipe system or a sprinkler system,
(i) a fire department pumper vehicle can be located adjacent to a hydrant, and
(ii) the unobstructed path of travel for the firefighter from the vehicle to the fire department connection is not more than 45 m, and
(b) for a building that is not sprinklered, a fire department pumper vehicle can be located in the access route so that the unobstructed path of travel for the firefighter is not more than,
(i) 45 m from the hydrant to the vehicle, and
(ii) 45 m from the vehicle to every opening in the building.
v1 O. Reg. 503/09
Later · viewing · 2010-01-01(1) Except as provided in Sentences (2) and (3), the requirements in Subsection 3.2.5. shall apply.
(2) Access routes for fire department vehicles shall be provided and shall be not less than 9 m wide.
(3) Hydrants shall be located in the access routes required in Sentence (2) so that,
(a) for a building provided with a fire department connection for a standpipe system or a sprinkler system,
(i) a fire department pumper vehicle can be located adjacent to a hydrant, and
(ii) the unobstructed path of travel for the firefighter from the vehicle to the fire department connection is not more than 45 m, and
(b) for a building that is not sprinklered, a fire department pumper vehicle can be located in the access route so that the unobstructed path of travel for the firefighter is not more than,
(i) 45 m from the hydrant to the vehicle, and
(ii) 45 m from the vehicle to every opening in the building.