3.1.19. — Above Ground Electrical Conductors

Content not available for this version.

3.1.19.1. — Clearance to Buildings

(1) Where a building is to be constructed in proximity to existing above ground electrical conductors of a voltage not less than 2.5 kV and not more than 46 kV,

(a) the building shall not be located beneath the conductors, and

(b) the horizontal clearance between the building and the maximum conductor swing shall be not less than 3 m.

(2) Where a building is to be constructed in proximity to existing above ground electrical conductors of a voltage more than 46 kV, the clearances between the building and the conductors shall conform to the requirements of CAN/CSA-C22.3 No.1, “Overhead Systems”.

Text · e-Laws consolidated snapshot

3.1.19.2. — Exception

(1) Article 3.1.19.1. does not apply to buildings containing electrical equipment and electrical installations used exclusively in the generation, transformation or transmission of electrical power or energy intended for sale or distribution to the public.

Text · e-Laws consolidated snapshot