OBC 2006 › Division B
12.3.4.2.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 12.3.4.2.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 12.3.4.2.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
New in this edition — no OBC 1997 predecessor
Base · O. Reg. 350/06 · ext← current
Original — base regulation
Content moved to SB-10, not yet covered
12.3.4.2. — Thermal Resistance of the Building Envelope
(1) Except as permitted in Sentences (2) and (3), the minimum thermal resistance of all walls, ceilings and floors that separate heated space from unheated space, the exterior air or the exterior soil shall conform to Table 12.3.4.2.A.
(2) Where the top of a foundation wall is less than 1 200 mm above the adjoining ground level, those portions of the foundation wall that are above ground may be insulated to the level required for the below grade portion of the foundation wall.
(3) The minimum thermal resistance of a slab-on-ground shall conform to Table 12.3.4.2.B.
(4) The maximum overall coefficient of heat transfer for windows that separate heated space from unheated space shall conform to Table 12.3.4.2.C.
(5) Except for swinging glass doors, the minimum thermal resistance of doors that separate heated space from unheated space shall be not less than RSI 0.7.
Editor's note
As filed in O. Reg. 350/06, the caption of Table 12.3.4.2.A. ends 'Based on Degree-Day Zones(1)' with the footnote marker '(1)' set inline and tight against the preceding word; the current e-Laws consolidation sets the marker as a superscript, raised rather than inline, with no amending regulation making the change. The footnote reference is the same, and this map preserves the caption as filed.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 | Column 3 |
Building Assembly | Minimum RSI Value of Assembly(2) | |
Zone 1 | Zone 2 | |
Less than 5000 | 5000 or more | |
degree-days | degree-days | |
Opaque wall assembly | 2.63 | 3.83 |
Wall assembly adjacent to unconditioned space | 1.61 | 2.02 |
Below grade wall(3) | 2.11 | 2.82 |
Roof assembly | 3.91 | 5.68 |
Floor assembly over unconditioned space | 4.52 | 4.52 |
Notes to Table 12.3.4.2.A.:
(1) Number of degree-days for individual locations are contained in Supplementary Standard SB-1.
(2) The thermal resistance determined for the building assembly shall take into account the thermal bridging in the assembly, as determined by Supplementary Standard SB-10.
(3) “RSI value” shown is for insulation only.
Column 1 | Column 2 | Column 3 | Column 4 |
Type of Slab-On-Ground | Position of Insulation | Length of Insulation, mm | Minimum RSI Value Required(1) |
Unheated | Horizontal | 600 | 3.17 |
1200 | 1.94 | ||
Vertical | 600 | 1.41 | |
1200 | 0.70 | ||
Heated | Horizontal | 600 | 3.52 |
1200 | 2.29 | ||
Vertical | 600 | 1.76 | |
1200 | 1.06 |
Notes to Table 12.3.4.2.B.:
(1) “RSI value” shown is for insulation only.
Column 1 | Column 2 |
Window-to-Wall Ratio | Maximum Overall Coefficient of Heat Transfer Required, W/ m²·°C |
less than 0.2 | 3.01 |
0.2 to 0.4 | 2.28 |
more than 0.4 | 1.70 |
Provenance
New in this edition — no OBC 1997 predecessor
Base · O. Reg. 350/06 · ext← current
Original — base regulation
Content moved to SB-10, not yet covered