12.3.3.3.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · renumbered from 9.38.3.1. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

Content moved to SB-12, not yet covered

12.3.3.3. — Thermal Resistance

(1) Except as provided in Articles 12.3.3.4. to 12.3.3.8., and except for doors, windows, skylights and other closures, the thermal resistance of each building assembly through any portion that does not include framing or furring shall conform to Table 12.3.3.3.

Editor's note

The note to Table 12.3.3.3. is reproduced here as filed in O. Reg. 350/06. The consolidated e-Laws text applies editorial formatting changes that were not enacted by any regulation; this map preserves the note as filed. The differences are: the heading "Notes to Table 12.3.3.3:" is in regular weight as filed and is rendered in bold on e-Laws, which also adds a trailing period to the table number ("12.3.3.3."); and the note marker "(1)" is plain text as filed and is rendered as a superscript on e-Laws.

Text · e-Laws consolidated snapshot

Table 12.3.3.3. Minimum Thermal Resistance of Building Assemblies Based on Degree-Day Zones Forming Part of Sentence 12.3.3.3.(1)

Column 1

Column 2

Column 3

Column 4

Building Assembly

Minimum RSI Value Required

Less than 5000

Zone 2

Electric

degree-days

5000 or more

Space Heating

degree-days

Zones 1 & 2

Ceiling below attic or roof space

7.24

7.24

9.00

Roof assembly without attic or roof space

5.21

5.21

5.21

Wall other than foundation wall

3.80

4.67

5.55

Foundation walls enclosing heated space

2.40

2.40

3.63

Floor, other than slab-on-ground

4.70

4.70

4.70

Slab-on-ground containing heating pipes, tubes, ducts or cables(1)

2.11

2.11

2.11

Slab-on-ground not containing heating pipes, tubes, ducts or cables(1)

1.76

1.76

2.11

Basement floor slabs located more than 600 mm below grade

Notes to Table 12.3.3.3:

(1) “RSI value” shown for slab-on-ground is for rigid insulation.