11.3.3.2. — Extensive Renovation

Comparing versions

Changed text stands out · unchanged is dimmed

v0 base

Earlier · viewing · 2006-12-31

(1) Where existing interior walls or ceilings or floor assemblies or roof assemblies are substantially removed in an existing building and new interior walls, ceilings, or floor assemblies are installed in the building, structural and fire-resistance elements shall be constructed in compliance with the requirements of the other Parts.

(2) Except as provided in Section 11.5., the proposed construction within an existing suite shall comply with the requirements of Section 3.8. where,

(a) the existing interior walls or floor assemblies within the suite are substantially removed in an existing building,

(b) new interior walls or floor assemblies are installed,

(c) the suite has an area greater than 300 m2, and

(d) the suite is located on,

(i) a floor area where the existing difference in elevation between the adjacent ground level and the floor level is not more than 200 mm., or

(ii) a normally occupied floor area which is accessible by a passenger type elevator or other platform equipped passenger elevating device from an entrance storey where the existing difference in elevation between the adjacent ground level and the entrance storey level is not more than 200 mm.

v1 O. Reg. 205/08

Later · 2010-04-01

(1) Where existing interior walls or ceilings or floor assemblies or roof assemblies are substantially removed in an existing building and new interior walls, ceilings, floor assemblies or roof assemblies are installed in the building, structural and fire-resistance elements shall be constructed in compliance with the requirements of the other Parts.

(2) Except as provided in Section 11.5., the proposed construction within an existing suite shall comply with the requirements of Section 3.8. where,

(a) the existing interior walls or floor assemblies within the suite are substantially removed in an existing building,

(b) new interior walls or floor assemblies are installed,

(c) the suite has an area greater than 300 m2, and

(d) the suite is located on,

(i) a floor area where the existing difference in elevation between the adjacent ground level and the floor level is not more than 200 mm., or

(ii) a normally occupied floor area which is accessible by a passenger type elevator or other platform equipped passenger elevating device from an entrance storey where the existing difference in elevation between the adjacent ground level and the entrance storey level is not more than 200 mm.

(3) Except as described in Sentence (4), where existing interior walls or ceilings or floor assemblies or roof assemblies are substantially removed on any storey in an existing building and new interior walls, ceilings, floor assemblies or roof assemblies are installed, the storey shall be sprinklered if,

(a) the storey will contain a Group C major occupancy, and

(b) the building is over 3 storeys in building height.

(4) Sentence (3) does not apply where the building,

(a) conforms to Subclause 3.2.2.44.(1)(a)(ii), and

(b) contains dwelling units having means of egress conforming to Sentence 3.3.4.4.(9).