1.1.3. — Building Size Determination

Content not available for this version.

1.1.3.1. — Building Size Determination of Building Divided by Firewalls

(1) Where a firewall divides a building, each portion of the building that is divided shall be considered as a separate building, except for the purposes of,

(a) a determination of gross area in Section 2.2. of Division C,

(b) a fire alarm and detection system in Sentence 3.2.4.2.(1) of Division B or Article 9.10.18.1. of Division B, and

(c) a plumbing system interconnected through a firewall.

Text · e-Laws consolidated snapshot

1.1.3.2. — Building Size Determination of Building Divided by Vertical Fire Separations

(1) Except as permitted in Sentence (2), if portions of a building are completely separated by a vertical fire separation that has a fire-resistance rating of at least 1 h and that extends through all storeys and service spaces of the separate portions, each separated portion may be considered to be a separate building for the purpose of determining building height if,

(a) each separated portion is not more than three storeys in building height and is used only for residential occupancies, and

(b) the unobstructed path of travel for a fire fighter from the nearest street to one entrance to each separated portion is not more than 45 m.

(2) The vertical fire separation in Sentence (1) may terminate at the floor assembly immediately above a basement if the basement conforms to Article 3.2.1.2. of Division B.