(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.9.11.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 9.9.11. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · renumbered to 9.9.12. — Pro
9.9.11. — Lighting
Content not available for this version.
9.9.11.1. — Application
(1) This Subsection applies to the lighting of all exits except those serving not more than 1 dwelling unit.
Text · e-Laws consolidated snapshot
9.9.11.2. — Required Lighting in Egress Facilities
(1) Every exit, public corridor or corridor providing access to exit for the public shall be equipped to provide illumination to an average level of not less than 50 lx at floor or tread level and at all points such as angles and intersections at changes of level where there are stairs or ramps.
Text · e-Laws consolidated snapshot
9.9.11.3. — Emergency Lighting
(1) Emergency lighting shall be provided in,
(a) exits,
(b) principal routes providing access to exit in an open floor area,
(c) corridors used by the public,
(d) underground walkways, and
(e) public corridors.
(2) Emergency lighting required in Sentence (1) shall be provided from a source of energy separate from the electrical supply for the building.
(3) Lighting required in Sentence (1) shall be designed to be automatically actuated for a period of not less than 30 min when the electric lighting in the affected area is interrupted.
(4) Illumination from lighting required in Sentence (1) shall be provided to average levels of not less than 10 lx at floor or tread level.
(5) Where incandescent lighting is provided, lighting equal to 1 W/m² of floor area shall be considered to meet the requirement in Sentence (4).
(6) Where self-contained emergency lighting units are used, they shall conform to CSA C22.2 No. 141-M, “Unit Equipment for Emergency Lighting”.
Text · e-Laws consolidated snapshot