9.9.1. — Scope

Content not available for this version.

9.9.1.1. — Application

(1) Stairways, handrails and guards in a means of egress shall conform to the requirements in Section 9.8. as well as to the requirements in this Section.

Text · e-Laws consolidated snapshot

9.9.1.2. — Fire Protection

(1) In addition to the fire protection requirements provided in Subsection 9.9.4., flame-spread ratings, fire-resistance ratings and fire-protection ratings for means of egress shall conform to Section 9.10.

Text · e-Laws consolidated snapshot

9.9.1.3. — Occupant Load

(1) The occupant load of a floor area or part of a floor area, or of a building or part of a building not having a floor area, shall be based on,

(a) 2 persons per sleeping room or sleeping area in a dwelling unit or suite, and

(b) for occupancies other than as described in Clause (a), the number of persons,

(i) for which the area is designed, or

(ii) determined from Table 3.1.17.1.

Text · e-Laws consolidated snapshot