9.34.4.5. — Underground Service

(1) For consumer services supplied underground,

(a) a 2 in. IPS steel, aluminum, copper or PVC conduit shall be attached to the bottom of the meter-mounting device and shall terminate in the earth at a point at least 900 mm below grade and a conduit bushing shall be attached to the conduit in the earth, and

(b) the conductors on the line side of the meter and those on the load side of the meter shall not be installed in the same conduit.

Text · e-Laws consolidated snapshot