9.34.4.3. — Location of Consumer Service Standpipe

(1) For an underground supply, the bottom of the consumer service standpipe shall be located not more than 3 m from the corner of the building.

(2) For an overhead supply, the top of the consumer service standpipe shall be located not more than 3 m from the corner of the building except that where this location does not permit a 4.5 m clearance at the point of attachment of the service conductors to the building, the top of the standpipe may be extended to a point not more than half way along the building.