OBC 2006 › Division B
9.25.2.4.
Version 1 — in force 2 April 2007
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.25.2.4.
- Version
- v1
80. (1) Subject to subsection (2), this Regulation comes into force on the day it is filed.
Read directly from the regulation's own commencement section.
O. Reg. 137/07 · commencement 80(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.25.2.4.
- Version
- v1
80. (1) Subject to subsection (2), this Regulation comes into force on the day it is filed.
Read directly from the regulation's own commencement section.
O. Reg. 137/07 · commencement 80(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · renumbered from 9.25.2.5. — Pro
Base · O. Reg. 350/06 · ext v0 →
O. Reg. 137/07, cl. 61 · ext ← current
In force 2007-04-02
OBC 2012 · continues as 9.25.2.4. — Pro
9.25.2.4. — Installation of Loose-Fill Insulation
(1) Except as provided in Sentences (2) to (6), loose-fill insulation shall be used on horizontal surfaces only.
(2) Where loose-fill insulation is installed in an unconfined sloped space, such as an attic space over a sloped ceiling, the supporting slope shall not be more than,
(a) 4.5 in 12 for mineral fibre or cellulose fibre insulation, and
(b) 2.5 in 12 for other types of insulation.
(3) Loose-fill insulation may be used in wood-frame walls of existing buildings.
(4) Where blown-in insulation is installed in above-ground or below-ground wood frame walls of new buildings,
(a) the density of the installed insulation shall be sufficient to preclude settlement,
(b) the insulation shall be installed behind a membrane that will permit visual inspection prior to installation of the interior finish,
(c) the insulation shall be installed in a manner that will not interfere with the installation of the interior finish, and
(d) no water shall be added to the insulation, unless it can be shown that the added water will not adversely affect other materials in the assembly.
(5) Water repellent loose-fill insulation may be used between the outer and inner wythes of masonry cavity walls.
(6) Where soffit venting is used, measures shall be taken,
(a) to prevent loose-fill insulation from blocking the soffit vents and to maintain an open path for circulation of air from the vents into the attic or roof space, and
(b) to minimize air flow into the loose-fill insulation near the soffit vents to maintain the thermal performance of the material.