9.22.9.4. — Heat Circulating Duct Openings

Comparing versions

Changed text stands out · unchanged is dimmed

v0 base

Earlier · 2006-12-31

(1) The clearance of combustible material above heat circulating duct openings from those openings shall be not less than,

(a) 300 mm where the combustible material projects more than 38 mm from the face, and

(b) 150 mm where the projection is less than 38 mm.

v1 O. Reg. 503/09

Later · viewing · 2010-01-01

(1) The clearance of combustible material above heat circulating duct openings from those openings shall be not less than,

(a) 300 mm where the combustible material projects not less than 38 mm from the face, and

(b) 150 mm where the projection is less than 38 mm.