OBC 2006 › Division B
9.22.9.4.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.22.9.4.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.22.9.4.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
Provenance
OBC 1997 · continues from 9.22.9.4. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
O. Reg. 503/09, cl. 172 · ext v1 →
In force 2010-01-01
Next: O. Reg. 503/09, cl. 172 · ext (not in force until 2010-01-01) v1 →
OBC 2012 · continues as 9.22.9.4. — Pro
9.22.9.4. — Heat Circulating Duct Openings
Comparing versions
Changed text stands out · unchanged is dimmed
v0 base
Earlier · viewing · 2006-12-31(1) The clearance of combustible material above heat circulating duct openings from those openings shall be not less than,
(a) 300 mm where the combustible material projects more than 38 mm from the face, and
(b) 150 mm where the projection is less than 38 mm.
v1 O. Reg. 503/09
Later · 2010-01-01(1) The clearance of combustible material above heat circulating duct openings from those openings shall be not less than,
(a) 300 mm where the combustible material projects not less than 38 mm from the face, and
(b) 150 mm where the projection is less than 38 mm.