80. (1) Subject to subsection (2), this Regulation comes into force on the day it is filed.
Read directly from the regulation's own commencement section.
O. Reg. 137/07 · commencement 80(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.15.4.2.
- Version
- v1
80. (1) Subject to subsection (2), this Regulation comes into force on the day it is filed.
Read directly from the regulation's own commencement section.
O. Reg. 137/07 · commencement 80(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · renumbered from 9.15.4.1. — Pro
Base · O. Reg. 350/06 · ext v0 →
O. Reg. 137/07, cl. 55 · ext ← current
In force 2007-04-02
OBC 2012 · continues as 9.15.4.2. — Pro
9.15.4.2. — Foundation Wall Thickness and Required Lateral Support
Comparing versions
Changed text stands out · unchanged is dimmed
v0 base
Earlier · 2006-12-31(1) Except as required in Sentence (2), the thickness of foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A. for walls not exceeding 2.5 m in unsupported height.
(2) The thickness of concrete in flat insulating concrete form foundation walls shall be not less than the greater of,
(a) 140 mm, or
(b) the thickness of the concrete in the wall above.
(3) Foundation walls made of flat insulating concrete form units shall be laterally supported at the top and at the bottom.
(4) Where average stable soils are encountered and wind loads on the exposed portion of the foundation are no greater than 0.70 kPa, the thickness and reinforcing of foundation walls made of reinforced concrete block and subject to lateral earth pressure shall conform to Table 9.15.4.2.B. and Sentences (5) to (10).
(5) For concrete block walls required to be reinforced, continuous vertical reinforcement shall,
(a) be provided at wall corners, wall ends, wall intersections, at changes in wall height, at the jambs of all openings and at movement joints,
(b) extend from the top of the footing to the top of the foundation wall,
(c) where foundation walls are laterally unsupported at the top, have not less than 600 mm embedment into the footing, and
(d) where foundation walls are laterally supported at the top, have not less than 50 mm embedment into the footing, if the floor slab does not provide lateral support at the wall base.
(6) Where foundation walls are laterally unsupported, the footing shall be designed according to Part 4 to resist overturning and sliding, if the maximum height of finished ground above the basement floor or crawl space ground cover exceeds 1.50 m.
(7) At the base of concrete block walls required to be reinforced and where the height of finished ground above the basement floor or crawl space ground cover exceeds 2.0 m, not less than one 15M intermediate vertical bar reinforcement shall be installed midway between adjacent continuous vertical reinforcement, and shall,
(a) extend to not less than 600 mm above the top of the footing, and
(b) have not less than 50 mm embedment into the footing, if the floor slab does not provide lateral support at the wall base.
(8) For concrete block walls required to be reinforced, a continuous horizontal bond beam containing at least one 15M bar shall be installed,
(a) along the top of the wall,
(b) at the sill and head of all openings greater than 1.20 m in width, and
(c) at structurally connected floors.
(9) In concrete block walls required to be reinforced, all vertical bar reinforcement shall be installed along the centre line of the wall.
(10) In concrete block walls required to be reinforced, ladder or truss type lateral reinforcement not less than 3.8 mm (No. 9 ASWG) shall be installed in the bed joint of every second masonry course.
v1 O. Reg. 137/07
Later · viewing · 2007-04-02(1) Except as required in Sentence (2), the thickness of foundation walls made of unreinforced concrete block or solid concrete and subject to lateral earth pressure shall conform to Table 9.15.4.2.A. for walls not exceeding 2.5 m in unsupported height.
(2) The thickness of concrete in flat insulating concrete form foundation walls shall be not less than the greater of,
(a) 140 mm, or
(b) the thickness of the concrete in the wall above.
(3) Foundation walls made of flat insulating concrete form units shall be laterally supported at the top and at the bottom.
(4) Where average stable soils are encountered and wind loads on the exposed portion of the foundation are no greater than 0.70 kPa, the thickness and reinforcing of foundation walls made of reinforced concrete block and subject to lateral earth pressure shall conform to Table 9.15.4.2.B. and Sentences (5) to (10).
(5) For concrete block walls required to be reinforced, continuous vertical reinforcement shall,
(a) be provided at wall corners, wall ends, wall intersections, at changes in wall height, at the jambs of all openings and at movement joints,
(b) extend from the top of the footing to the top of the foundation wall,
(c) where foundation walls are laterally unsupported at the top, have not less than 600 mm embedment into the footing, and
(d) where foundation walls are laterally supported at the top, have not less than 50 mm embedment into the footing, if the floor slab does not provide lateral support at the wall base.
(6) Where foundation walls are laterally unsupported, the footing shall be designed according to Part 4 to resist overturning and sliding, if the maximum height of finished ground above the basement floor or crawl space ground cover exceeds 1.50 m.
(7) At the base of concrete block walls required to be reinforced and where the height of finished ground above the basement floor or crawl space ground cover exceeds 2.0 m, not less than one 15M intermediate vertical bar reinforcement shall be installed midway between adjacent continuous vertical reinforcement, and shall,
(a) extend to not less than 600 mm above the top of the footing, and
(b) have not less than 50 mm embedment into the footing, if the floor slab does not provide lateral support at the wall base.
(8) For concrete block walls required to be reinforced, a continuous horizontal bond beam containing at least one 15M bar shall be installed,
(a) along the top of the wall,
(b) at the sill and head of all openings greater than 1.20 m in width, and
(c) at structurally connected floors.
(9) In concrete block walls required to be reinforced, all vertical bar reinforcement shall be installed along the centre line of the wall.
(10) In concrete block walls required to be reinforced, ladder or truss type lateral reinforcement not less than 3.8 mm (No. 9 ASWG) shall be installed in the bed joint of every second masonry course.
Provenance
OBC 1997 · renumbered from 9.15.4.1. — Pro
Base · O. Reg. 350/06 · ext v0 → comparing ×
O. Reg. 137/07, cl. 55 · ext ← current
In force 2007-04-02
OBC 2012 · continues as 9.15.4.2. — Pro