CodeChronicle

OBC 2006 Division B

9.10.18.4.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · renumbered from 9.10.17.4. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · renumbered to 9.10.18.5. — Pro

9.10.18.4. — Smoke Detectors in Recirculating Air Handling Systems

(1) Except for a recirculating air system serving not more than 1 dwelling unit, where a fire alarm system is required to be installed, every recirculating air handling system shall be designed to prevent the circulation of smoke upon a signal from a duct-type smoke detector where such system supplies more than one suite on the same floor or serves more than 1 storey.

Text · e-Laws consolidated snapshot