9.10.18.2. — Fire Alarm System Required

(1) Except as provided in Sentence (2), a fire alarm system shall be installed,

(a) in every building that contains more than 3 storeys, including storeys below the first storey,

(b) where the total occupant load exceeds 300, or

(c) when the occupant load for any major occupancy in Table 9.10.18.2. is exceeded.

(2) A fire alarm system is not required in a residential occupancy where an exit or public corridor serves not more than 4 suites or where each suite has direct access to an exterior exit facility leading to ground level.

Text · e-Laws consolidated snapshot

Table 9.10.18.2. Maximum Occupant Load for Buildings without Fire Alarm Systems Forming Part of Sentence 9.10.18.2.(1)

Column 1

Column 2

Major Occupancy Classification

Occupant Load Above which

Fire Alarm System is Required

Residential

10 (sleeping accommodation)

Business and personal services, mercantile

150 above or below the first storey

Low- or medium-hazard industrial

75 above or below the first storey