OBC 2006 › Division B
9.10.18.2.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.10.18.2.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.10.18.2.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · renumbered from 9.10.17.2. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 9.10.18.2. — Pro
9.10.18.2. — Fire Alarm System Required
(1) Except as provided in Sentence (2), a fire alarm system shall be installed,
(a) in every building that contains more than 3 storeys, including storeys below the first storey,
(b) where the total occupant load exceeds 300, or
(c) when the occupant load for any major occupancy in Table 9.10.18.2. is exceeded.
(2) A fire alarm system is not required in a residential occupancy where an exit or public corridor serves not more than 4 suites or where each suite has direct access to an exterior exit facility leading to ground level.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 |
Major Occupancy Classification | Occupant Load Above which Fire Alarm System is Required |
Residential | 10 (sleeping accommodation) |
Business and personal services, mercantile | 150 above or below the first storey |
Low- or medium-hazard industrial | 75 above or below the first storey |