240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 9.10.15.4.
- Version
- v1
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
New in this edition — no OBC 1997 predecessor
Base · O. Reg. 350/06 · ext v0 →
O. Reg. 503/09, cl. 149(2) · ext ← current
In force 2010-01-01
OBC 2012 · continues as 9.10.15.4. — Pro
9.10.15.4. — Glazed Openings in Exposing Building Face
Comparing versions
Changed text stands out · unchanged is dimmed
v0 base
Earlier · 2006-12-31(1) Except as provided in Sentences (3) to (5), the maximum area of glazed openings in an exposing building face shall,
(a) conform to Table 9.10.15.4.,
(b) conform to Subsection 3.2.3., or
(c) be equal to or less than the limiting distance squared.
(2) Where the exposing building face is divided into individual portions as described in Subclause 9.10.15.2.(1)(b)(iii),
(a) the maximum glazed area of each individual portion shall be determined in accordance with Sentence (1),
(b) the maximum aggregate glazed area for the entire exposing building face shall be the sum of the individual maximum glazed areas determined from Clause (a), and
(c) except as required in Sentence (4), the maximum aggregate glazed area determined in Clause (b) is permitted to be distributed anywhere on the exposing building face.
(3) The limits on area of glazed openings shall not apply to the exposing building face of a dwelling unit facing a detached garage or accessory building where,
(a) the detached garage or accessory building serves only one dwelling unit,
(b) the detached garage or accessory building is located on the same property as that dwelling unit, and
(c) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property.
(4) Except as permitted in Sentence (5), openings in a wall having a limiting distance of less than 1.2 m shall be protected by closures, of other than wired glass or glass block, whose fire-protection rating is in conformance with the fire-resistance rating required for the wall.
(5) An opening in an exposing building face not more than 130 cm2 shall not be considered an unprotected opening.
v1 O. Reg. 503/09
Later · viewing · 2010-01-01(1) Except as provided in Sentences (3) to (5), the maximum area of glazed openings in an exposing building face shall,
(a) conform to Table 9.10.15.4.,
(b) conform to Subsection 3.2.3. as if the glazed openings were unprotected openings, or
(c) be equal to or less than the limiting distance squared.
(2) Where the limits on the area of glazed openings are determined for individual portions of the exterior wall, as described in Subclause 9.10.15.2.(1)(b)(iii), the maximum aggregate area of glazed openings for any portion shall not exceed the values in the row of Table 9.10.15.4. for the total area of the entire exposing building face based on the limiting distance of the individual portion.
(3) The limits on area of glazed openings shall not apply to the exposing building face of a dwelling unit facing a detached garage or accessory building where,
(a) the detached garage or accessory building serves only one dwelling unit,
(b) the detached garage or accessory building is located on the same property as that dwelling unit, and
(c) the dwelling unit served by the detached garage or accessory building is the only major occupancy on the property.
(4) Except as permitted in Sentence (5), openings in a wall having a limiting distance of less than 1.2 m shall be protected by closures, of other than wired glass or glass block, whose fire-protection rating is in conformance with the fire-resistance rating required for the wall.
(5) An opening in an exposing building face not more than 130 cm2 shall not be considered an unprotected opening.
Provenance
New in this edition — no OBC 1997 predecessor
Base · O. Reg. 350/06 · ext v0 → comparing ×
O. Reg. 503/09, cl. 149(2) · ext ← current
In force 2010-01-01
OBC 2012 · continues as 9.10.15.4. — Pro