9.10.15.3. — Inadequate Firefighting Facilities

Comparing versions

Changed text stands out · unchanged is dimmed

v0 base

Earlier · 2006-12-31

(1) Where there is no fire department or where a fire department is not organized, trained and equipped to meet the needs of the community, the required limiting distance determined from Sentences 9.10.15.4.(2), (5) and (6) and Sentence 9.10.15.5.(6), shall be doubled for a building that is not sprinklered.

v1 O. Reg. 503/09

Later · viewing · 2010-01-01

(1) Where there is no fire department or where a fire department is not organized, trained and equipped to meet the needs of the community, the required limiting distance determined from Sentences 9.10.15.4.(2) and (5) and Sentence 9.10.15.5.(6), shall be doubled for a building that is not sprinklered.