7.6.5.2. — Showers

(1) Except as provided for in Sentence (2) and (3), all valves supplying fixed location shower heads, shall be individually pressure-balanced or thermostatic-mixing valves, conforming to CAN/CSA-B125, “Plumbing Fittings”.

(2) An individually pressure-balanced or thermostatic-mixing valve shall not be required for  showers if a single temperature water supply for such showers is controlled by a master thermostatic-mixing valve conforming to CAN/CSA-B125, “Plumbing Fittings”.

(3) Deck-mounted, hand-held, flexible-hose spray attachments are exempt from the thermal shock requirements of Sentence (1).

(4) Pressure-balanced or thermostatic-mixing valves shall be,

(a) designed so that the outlet temperature does not exceed 49°C, or

(b) equipped with high-limit stops which shall be adjusted to a maximum hot water setting of 49°C.

Editor's note

This map follows the as-filed text of O. Reg. 350/06 for Article 7.6.5.2. of Division B, in which Sentence (1) refers to 'Sentence (2) and (3)' using the singular 'Sentence'. The e-Laws consolidation editorially renders the reference in the plural as 'Sentences', with no amending regulation making the change. This map preserves the as-filed wording.