7.5.9.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

New in this edition — no OBC 1997 predecessor

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · continues as 7.5.9. — Pro

7.5.9. — Air Admittance Valves

Content not available for this version.

7.5.9.1. — Air Admittance Valve as a Vent Terminal

(1) Individual vents may terminate with a connection to an air admittance valve as provided in Articles 7.5.9.2.v1 and 7.5.9.3.v1

Text · e-Laws consolidated snapshot

7.5.9.2. — Air Admittance Valves

(1) Air admittance valves shall only be used to vent,

(a) fixtures in buildings undergoing renovation, and

(b) installations where connection to a vent may not be practical.

(2) The air admittance valves shall be located,

(a) above the flood level rim of the fixture it serves,

(b) within the maximum developed length permitted for the vent,

(c) not less than 150 mm above insulation materials, and

(d) installed in a location not subject to back pressure.

(3) Air admittance valves shall,

(a) only vent fixtures located on the same storey, and

(b) be connected to the horizontal fixture drain.

Text · e-Laws consolidated snapshot

7.5.9.3. — Installation Conditions

(1) Air admittance valves shall not be installed in supply or return air plenums, or in locations where they may be exposed to freezing temperatures.

(2) Air admittance valves shall be installed in accordance with the manufacturer’s installation instructions.

(3) Air admittance valves shall be rated for the size of vent pipe to which they are connected.

(4) Installed air admittance valves shall be,

(a) accessible, and

(b) located in a space that allows air to enter the valve.

(5) Every drainage system shall have one vent that terminates to open air in conformance with Sentence 7.5.6.2.(1).