7.5.8.1. — Hydraulic Loads Draining to Wet Vents

(1) The hydraulic load that drains to a wet vent shall conform to Table 7.5.8.1.

(2) When determining the size of a wet vent, the hydraulic load from the most downstream fixture or symmetrically connected fixtures shall not be included.

Text · e-Laws consolidated snapshot

Table 7.5.8.1. Maximum Permitted Hydraulic Loads Drained to a Wet Vent Forming Part of Articles 7.5.2.1. and 7.5.8.1.

Column 1

2

3

Size of Wet Vent, in.

Maximum Hydraulic Load, Fixture Units

Not Serving Water Closets

Serving Not More Than Two Water Closets

Fixtures Other Than Water Closets

1 ½

2

N/A

2

4

3

3

12

8

4

36

14

5

N/A

18

6

N/A

23