OBC 2006 › Division B
7.5.6.3.
Version 1 — in force 1 January 2010
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 7.5.6.3.
- Version
- v1
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 7.5.6.3.
- Version
- v1
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · renumbered from 7.5.5.3. — Pro
Base · O. Reg. 350/06 · ext v0 →
O. Reg. 503/09, cl. 108 · ext ← current
In force 2010-01-01
OBC 2012 · continues as 7.5.6.3. — Pro
7.5.6.3. — Location of Vent Pipes
Comparing versions
Changed text stands out · unchanged is dimmed
v0 base
Earlier · 2006-12-31(1) Except as provided in Sentences (2) and (3), a vent pipe that protects a fixture trap shall be located so that,
(a) the developed length of the trap arm is not less than twice the size of the fixture drain,
(b) the total fall of the trap arm is not greater than its inside diameter, and
(c) the trap arm does not have a cumulative change in direction of more than 135°.
(2) The trap arm of water closets, S-trap standards or any other fixture that also discharges vertically and depends on siphonic action for its proper functioning shall not have a cumulative change in direction of more than 225°.
(3) A vent pipe that protects a water closet or any other fixture that also depends on siphonic action for its proper functioning shall be located so that the distance between the connections of the fixture drain to the fixture and the vent pipe shall not exceed,
(a) 1 000 mm in the vertical plane, and
(b) 3 m in the horizontal plane.
(4) The maximum length and minimum slope of every trap arm shall conform to Table 7.5.6.3.
(5) The vent pipe from a water closet or any other fixture that has an integral siphonic flushing action may be connected to the vertical leg of its drainage pipe.
v1 O. Reg. 503/09
Later · viewing · 2010-01-01(1) Except as provided in Sentences (2) and (3), a vent pipe that protects a fixture trap shall be located so that,
(a) the developed length of the trap arm is not less than twice the size of the fixture drain,
(b) the total fall of the trap arm is not greater than its inside diameter, and
(c) the trap arm does not have a cumulative change in direction of more than 135°.
(2) The trap arm of water closets, S-trap standards or any other fixture that also discharges vertically and depends on siphonic action for its proper functioning shall not have a cumulative change in direction of more than 225°.
(3) A vent pipe that protects a water closet or any other fixture that also depends on siphonic action for its proper functioning shall be located so that the distance between the connections of the fixture drain to the fixture and the vent pipe shall not exceed,
(a) 1 000 mm in the vertical plane, and
(b) 3 m in the horizontal plane.
(4) The maximum length and minimum slope of every trap arm shall conform to Table 7.5.6.3.
(5) The vent pipe from a water closet or any other fixture that has an integral siphonic flushing action may be connected to the vertical leg of its drainage pipe.
Provenance
OBC 1997 · renumbered from 7.5.5.3. — Pro
Base · O. Reg. 350/06 · ext v0 → comparing ×
O. Reg. 503/09, cl. 108 · ext ← current
In force 2010-01-01
OBC 2012 · continues as 7.5.6.3. — Pro