7.4.9.2. — Serving Water Closets

(1) The size of every drainage pipe that serves a water closet shall be at least 3 in.

(2) The size of every horizontal drainage pipe downstream of the third water closet fixture drain connection shall be at least 4 in.

(3) The size of every soil stack that serves more than 6 water closets shall be at least 4 in.

(4) The discharge pipe serving a macerating toilet shall be not less than 3/4 in. size with a hydraulic load of 4 fixture units.