7.4.8. — Minimum Slope and Length of Drainage Pipes

Content not available for this version.

7.4.8.1. — Minimum Slope

(1) Except as provided in Sentences (2) and (3), every drainage pipe that has a size of 3 in. or less, and every fixture drain shall have a downward slope in the direction of flow of at least 1 in 50.

(2) Sentence (1) does not apply to a force main.

(3) Where it is not possible to comply with Sentence (1), a lesser slope may be used if it will produce a gravity flow of not less than 0.6 m per second.

Text · e-Laws consolidated snapshot

7.4.8.2. — Length of Fixture Outlet Pipes

(1) Except for fixture outlet pipes installed in conformance with Sentence 7.4.5.1.(3), the developed length of every fixture outlet pipe shall not exceed 1 200 mm.

Text · e-Laws consolidated snapshot