7.3.6.6.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 7.3.6.6. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · continues as 7.3.6.6. — Pro

7.3.6.6. — Final Tests

(1) Where a final test is made,

(a) every trap shall be filled with water,

(b) the bottom of the system being tested shall terminate at the building trap, test plug or cap,

(c) except as provided in Sentence (2), smoke from smoke-generating machines shall be forced into the system,

(d) when the smoke appears from all roof terminals they shall be closed, and

(e) a pressure equivalent to a 25 mm water column shall be maintained for 15 min without the addition of more smoke.

(2) The smoke referred to in Clauses (1)(c) and (d) may be omitted provided the roof terminals are closed and the system is subjected to an air pressure equivalent to a 25 mm water column maintained for 15 min without the addition of more air.