7.2.11.4. — Required Check Valve

(1) Where a water service pipe is supplied with water by more than one drinking-water system, a check valve shall be installed at each connection with a drinking-water system.

(2) Where a fire service main is supplied with water by more than one source, a check valve shall be installed at each connection with a source of water.

Editor's note

This map follows the as-filed text of O. Reg. 350/06 for Article 7.2.11.4. of Division B, which uses the hyphenated defined term 'drinking-water system' (twice). As of its July 1, 2007 re-render the e-Laws consolidation de-hyphenates both occurrences to 'drinking water system', with no amending regulation making the change — no regulation in force on that date amends this Article. This map preserves the as-filed hyphenation.