OBC 2006 › Division B
6.2.9.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 6.2.9.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 6.2.9.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next edition replaced it. What follows is that edition’s base regulation’s commencement — the takeover that ended this one.
(1) Subject to Sentences (2) and (3), this Regulation comes into force on January 1, 2014.
Read directly from the regulation's own commencement section.
O. Reg. 332/12 · commencement 4.4.1.1(1)
Provenance
OBC 1997 · continues from 6.2.9. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 6.2.9. — Pro
6.2.9. — Piping for Heating and Cooling Systems
Content not available for this version.
6.2.9.1. — Piping Materials and Installation
(1) Piping shall be made from materials designed to withstand the effects of temperatures and pressures that may occur in the system.
(2) Every pipe used in a heating or air-conditioning system shall be installed to allow for expansion and contraction due to temperature changes.
(3) Supports and anchors for piping in a heating or air-conditioning system shall be designed and installed to ensure that undue stress is not placed on the supporting structure.
Text · e-Laws consolidated snapshot
6.2.9.2. — Insulation and Coverings
(1) Insulation and coverings on pipes shall be composed of material suitable for the operating temperature of the system to withstand deterioration from softening, melting, mildew and mould.
(2) Insulation and coverings on pipes in which the temperature of the fluid exceeds 120°C,
(a) shall be made of noncombustible material, or
(b) shall not flame, glow, smoulder or smoke when tested in accordance with the method of test ASTM C411, “Hot-Surface Performance of High-Temperature Thermal Insulation”, at the maximum temperature to which such insulation or covering is to be exposed in service.
(3) Except as provided in Sentence (7), where combustible insulation is used on piping in a horizontal or vertical service space, the insulation and coverings on such pipes shall have a flame-spread rating throughout the material of not more than 25 in buildings of noncombustible construction and not more than 75 in buildings of combustible construction.
(4) Except as provided in Sentence (7), insulation and coverings on piping located in rooms and spaces other than the service spaces described in Sentence (3) shall have a flame-spread rating of not more than that required for the interior finish for the ceiling of the room or space.
(5) Except as provided in Sentence (7), where combustible insulation and covering is used on piping in buildings described in Subsection 3.2.6.v1, they shall have a smoke developed classification of not more than 100.
(6) Exposed piping or equipment subject to human contact shall be insulated so that the temperature of the exposed surface does not exceed 70°C.
(7) No flame-spread rating or smoke developed classification limitations are required where combustible insulation and coverings are used on piping when such piping is,
(a) located within a concealed space in a wall,
(b) located in a floor slab, or
(c) enclosed in a noncombustible raceway or conduit.
Text · e-Laws consolidated snapshot
6.2.9.3. — Clearances
(1) Clearances between combustible material and bare pipes carrying steam or hot water shall conform to Table 6.2.9.3.
Editor's note
Between the filing (December 21, 2009) and commencement (January 1, 2010) of O. Reg. 503/09, the e-Laws consolidation publishes an interim version of Table 6.2.9.3. that differs from the in-force version only in table layout (column width), with no change to in-force content. This map does not reproduce that presentation-only interim version.
Text · e-Laws consolidated snapshot
Column 1 | Column 2 |
Steam or Water Temperature, °C | Minimum Clearance, mm |
not above 95 | no clearance |
above 95 to 120 | 15 |
above 120 | 25 |
6.2.9.4. — Surface Temperature
(1) The exposed surface temperature of a steam or hot water radiator shall not exceed 70°C unless precautions are taken to prevent human contact.
Text · e-Laws consolidated snapshot
6.2.9.5. — Protection
(1) Where a pipe carrying steam or hot water at a temperature above 120°C passes through a combustible floor, ceiling or wall, the construction shall be protected by a sleeve of metal or other noncombustible material not less than 50 mm larger in diameter than the pipe.
(2) Unprotected steam or hot water pipes that pass through a storage space shall be covered with not less than 25 mm of noncombustible insulation to prevent direct contact with the material stored.
Text · e-Laws consolidated snapshot
6.2.9.6. — Piping in Shafts
(1) Where piping for heating or air-conditioning systems is enclosed in a shaft, the requirements of Article 3.6.3.1. for shafts shall apply.
Text · e-Laws consolidated snapshot
Provenance
OBC 1997 · continues from 6.2.9. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
OBC 2012 · continues as 6.2.9. — Pro