6.2.4.2.

Version 0 — in force 31 December 2006

In force
Verified · covered Verified against the 2006-12-31–2007-04-01 consolidation, whose range covers the query date. How to read this

Provenance

OBC 1997 · continues from 6.2.4.2. — Pro

Base · O. Reg. 350/06 · ext← current

Original — base regulation

OBC 2012 · continues as 6.2.4.2. — Pro

6.2.4.2. — Duct Design

(1) Materials in supply ducts shall conform to Article 6.2.3.2.

(2) Galvanized steel or aluminum supply ducts shall conform to Table 6.2.4.2.

(3) The design of fitting for ducts shall conform to SMACNA, “HVAC Duct Construction Standards - Metal and Flexible”, except that metal thickness shall conform to Table 6.2.4.2.

Text · e-Laws consolidated snapshot

Table 6.2.4.2. Minimum Metal Thickness of Ducts Forming Part of Sentence 6.2.4.2.(2)

Column 1

Column 2

Column 3

Column 4

Column 5

Type of Duct

Maximum

Maximum

Minimum Metal Thickness, mm

Diameter,

Width or Depth,

Duct Material

mm

mm

Galvanized Steel

Aluminum

Round ducts serving single dwelling units

125 or less

---

0.254

0.30

Round

350

---

0.33

0.30

over 350

---

0.41

0.41

Rectangular, enclosed

---

350

0.33

0.30

---

over 350

0.41

0.41

Rectangular, not enclosed, for single dwelling units, with required clearance up to 12 mm

---

350

0.33

0.41

---

over 350

0.41

0.48

Rectangular, not enclosed, with required clearance of more than 12 mm

---

350

0.41

0.41

---

over 350

0.48

0.48