6.2.2.1. — Required Ventilation

(1) Except as provided in Sentence (3), all buildings shall be ventilated in accordance with this Part.

(2) Except in storage garages and repair garages covered by Article 6.2.2.3., the rates at which outdoor air is supplied in buildings by ventilation systems shall be not less than the rates required by ANSI/ASHRAE 62, “Ventilation for Acceptable Indoor Air Quality”.

(3) Self-contained mechanical ventilation systems that serve only one dwelling unit and that conform to the requirements of Subsection 9.32.3. shall be considered to satisfy the requirements of this Article.

(4) Live/work units shall be mechanically ventilated in accordance with the requirements of Sentence (1).