OBC 2006 › Division B
6.2.2.1.
Version 0 — in force 31 December 2006
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 6.2.2.1.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
This looks wrong
Tell us what is wrong and we will verify & correct our mapping.
- Edition
- OBC_2006
- Division
- B
- Provision
- 6.2.2.1.
- Version
- v0
(1) This Regulation comes into force on December 31, 2006.
Read directly from the regulation's own commencement section.
O. Reg. 350/06 · commencement 2.2.1.1(1)
This version stayed in force until the next one commenced. What follows is that next version’s commencement — the event that ended this one.
240. (1) Subject to subsections (2), (3), (4), (5), (6) and (7), this Regulation comes into force on the later of January 1, 2010 and the day this Regulation is filed.
Read directly from the regulation's own commencement section.
O. Reg. 503/09 · commencement 240(1)
Provenance
OBC 1997 · renumbered from 3.7.3.1. — Pro
OBC 1997 · continues from 6.2.2.1. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
O. Reg. 503/09, cl. 74 · ext v1 →
In force 2010-01-01
Next: O. Reg. 503/09, cl. 74 · ext (not in force until 2010-01-01) v1 →
OBC 2012 · continues as 6.2.2.1. — Pro
6.2.2.1. — Required Ventilation
(1) Except as provided in Sentence (3), all buildings shall be ventilated in accordance with this Part.
(2) Except in storage garages and repair garages covered by Article 6.2.2.3., the rates at which outdoor air is supplied in buildings by ventilation systems shall be not less than the rates required by ANSI/ASHRAE 62, “Ventilation for Acceptable Indoor Air Quality”.
(3) Self-contained mechanical ventilation systems that serve only one dwelling unit and that conform to the requirements of Subsection 9.32.3. shall be considered to satisfy the requirements of this Article.
(4) Live/work units shall be mechanically ventilated in accordance with the requirements of Sentence (1).
Text · e-Laws consolidated snapshot
Provenance
OBC 1997 · renumbered from 3.7.3.1. — Pro
OBC 1997 · continues from 6.2.2.1. — Pro
Base · O. Reg. 350/06 · ext← current
Original — base regulation
O. Reg. 503/09, cl. 74 · ext v1 →
In force 2010-01-01 compare
Next: O. Reg. 503/09, cl. 74 · ext (not in force until 2010-01-01) v1 →
OBC 2012 · continues as 6.2.2.1. — Pro