6.2.1.1. — Good Engineering Practice

Comparing versions

Changed text stands out · unchanged is dimmed

v0 base

Earlier · 2006-12-31

(1) Heating, ventilating and air-conditioning systems, including related mechanical refrigeration systems, shall be designed, constructed and installed to conform to good engineering practice appropriate to the circumstances such as described in,

(a) the ASHRAE Handbooks as follows:

(i) Fundamentals,

(ii) Refrigeration,

(iii) HVAC Applications,

(iv) HVAC Systems and Equipment, and

(v) ANSI/ASHRAE/IESNA 90.1, “Energy Efficient Design of New Buildings Except Lowrise Residential Buildings”.

(b) the CAN/CSA-F280-M, “Determining the Required Capacity of Residential Space Heating and Cooling Appliances”, and the outside winter design temperatures shall conform to Supplementary Standard SB-1,

(c) the CAN/CSA-F326-M, “Residential Mechanical Ventilation Systems”,

(d) the NFPA Fire Codes,

(e) the HRAI Digest,

(f) the Hydronics Institute Manuals,

(g) the SMACNA Manuals,

(h) the ACGIH Industrial Ventilation Manual,

(i) CAN/CSA-Z317.2, “Special Requirements for Heating, Ventilation, and Air Conditioning (HVAC) Systems in Health Care Facilities”, and

(j) the Model National Energy Code for Buildings.

v1 O. Reg. 137/07

Later · viewing · 2007-04-02

(1) Heating, ventilating and air-conditioning systems, including related mechanical refrigeration systems, shall be designed, constructed and installed to conform to good engineering practice appropriate to the circumstances such as described in,

(a) the ASHRAE Handbooks as follows:

(i) Fundamentals,

(ii) Refrigeration,

(iii) HVAC Applications,

(iv) HVAC Systems and Equipment, and

(v) ANSI/ASHRAE/IESNA 90.1, “Energy Standard for Buildings Except Low-Rise Residential Buildings”,

(b) the CAN/CSA-F280-M, “Determining the Required Capacity of Residential Space Heating and Cooling Appliances”, and the outside winter design temperatures shall conform to Supplementary Standard SB-1,

(c) the CAN/CSA-F326-M, “Residential Mechanical Ventilation Systems”,

(d) the NFPA Fire Codes,

(e) the HRAI Digest,

(f) the Hydronics Institute Manuals,

(g) the SMACNA Manuals,

(h) the ACGIH Industrial Ventilation Manual,

(i) CAN/CSA-Z317.2, “Special Requirements for Heating, Ventilation, and Air Conditioning (HVAC) Systems in Health Care Facilities”, and

(j) the CCBFC, “Model National Energy Code for Buildings”.